The Kyoritsu 3128 12kV High Voltage Insulation Tester is a microprocessor controlled tester and includes various diagnostic functions that provide the ability to test the polarization index (PI), the dielectric absorption ratio (DAR) and the dielectric discharge (DD). Step voltage (SV) measurements can be made where successive voltage increments are implemented to test the degradation of insulation.7
Using the Kyoritsu 3128 High Voltage Insulation Tester.Insulation resistance can be measured up to 35TΩ, with test voltages up to 12kV
Kyoritsu 3128 12kV High Voltage Insulation Te Specifications:
Insulation resistance (*): Accuracy is not guaranteed with setting of 250V or less
Rated voltage | 500V | 1000V | 2500V | 5000V | 10000V | 12000V |
---|---|---|---|---|---|---|
Max measurement value | 500GΩ | 1TΩ | 2.5TΩ | 5TΩ | 35TΩ | |
Accuracy | 400k~50GΩ ±5%rdg±3dgt (*) |
800k~100GΩ 5%rdg±3dgt | 2M~250GΩ ±5%rdg±3dgt | 4M~500GΩ ±5%rdg±3dgt | 8M~1TΩ ±5%rdg±3dgt | |
50G~500GΩ ±20%rdg (*) |
100G~1TΩ ±20%rdg |
250G~2.5TΩ ±20%rdg |
500G~5TΩ ±20%rdg |
1T~10TΩ ±20%rdg |
||
10T – 35TΩ Values are displayed, but accuracy isn’t guaranteed |
||||||
Short circuit current | Max 5.0mA | |||||
Load resistor to output rated voltage | 0.5MΩ or more | 1MΩ or more | 2.5MΩ or more | 5MΩ or more | 20MΩ or more | 24MΩ or more |
Output voltage
Rated voltage | 500V | 1000V | 2500V | 5000V | 10000V | 12000V |
---|---|---|---|---|---|---|
Monitor accuracy | ±10%±20V | ±10%±20V | ±10%±20V | ±10%±20V | ±10%±20V | ±10%±20V |
Output accuracy | 0 – +20% | 0 – +10% | 0 – +10% | 0 – +10% | -5 – +5% | -5 – +5% |
Selectable range | 50 – 600V (in steps of 5V) |
610 – 1200V (in steps of 10V) | 1225 – 3000V (in steps of 25V) | 3050 – 6000V (in steps of 50V) | 6100 – 10000V (in steps of 100V) |
10100 – 12000V (in steps of 100V) |
Voltage measurement
Measuring range | DCV:±30 ~ ±600V、ACV:30 ~ 600V (50/60Hz) |
---|---|
Accuracy | ±2%rdg±3dgt |
Current measurement
Measuring range | 5.00nA – 2.40mA (Depending on the insulation resistance) |
---|
Capacitance measurement
Measuring range | 5.0nF ~ 50.0μF (500V/1000V/2500V/5000V) |
5.0nF – 1.0µF (display range: 5.0nF – 50.0µF) (10000V/12000V) |
---|---|---|
Accuracy | ±5%rdg±5dgt |
General
Applicable standards | IEC 61010-1 CAT IV 600V Pollution degree 2, IEC 61010-031, IEC 61326, IEC 60529 (IP64): with the lid closed. |
---|---|
Operating temperature & humidity range | -10ºC – Relative humidity 85% or less 50ºC /(when operating with an external power supply, no condensation) 0ºC – 40ºC /Relative humidity 85% or less (when operating with battery, no condensation) |
Storage temperature & humidity range | -20ºC – 60ºC / Relative humidity 75% or less (no condensation) |
Power source | Rechargeable Lead storage battery (12V)* Charging time: approx. 8 hours / AC Power supply (100V – 240V, 50/60Hz) * Continuous measuring time: approx. 4 hours (a load of 100MΩ at the Insulation resistance 12000V Range.) approx. 2 hours (Max current consumption in range while rated currents are maintained.) |
Dimensions | 330 (L) × 410 (W) × 180 (D) mm *Instrument and Hard case |
Weight | 9kg approx. (including battery) *Instrument and Hard case |
Included Accessories | 7170 (Main cord), 7224A (Earth cord), 7225A (Guard cord), 7226A (Line probe), 7227A (Line probe with alligator clip), 8029 (Extension prod), 8212-USB-W (USB adaptor with KEW Windows (Software)), Instruction manual |
Optional Accessories | 7254 (Longer Line probe with alligator clip) |