Leda Electronics Logo. Western  Australia's largest distributor of Test Instruments Leda Electronics Showing The Way
 
Clamp-On Meters > Model 30031A and 30032A
Yokogawa Test and Measurement Logo

Yokogawa Clamp-On Meter for AC Leakage Current Measurements

Model 30031A and 30032A
Clamp-On Tester for AC Leakage Current Measurements

Yokogawwa Model 30031A and 30032A  Clamp Meter for AC leakage Current Measurements

Yokogawa 30031 Features

bullet

Can measure leakage currents of 1mA, which is useful for checking the insulation of low-voltage circuits and electrical components.

bullet

Can measure a broad range of currents from leakage currents (at a resolution of 0.001 mA) to load currents up to 60A.

bullet

Typical influence (on the current value of an adjacent cable) from an external magnetic field is 0.0005%.

bullet

Filter function can cut off the harmonics - current components from 2nd order (for 30032A only).

bullet

The design of the clamp lever enables smooth opening/closing of the clamp even for thick cables of 40mm in diameter.

bullet

Approved for conformity to safety standards EN61010-1, EN61010-2-032 (CAT III 300V, pollution degree 2).

 
Yokogawa Model 30031A and 30032A Specifications
AC Current Measurement (for 30031A)
Range Resolution Accuracy Maximum Allowable Current
3mA 0.001mA 0.010<1<32.70mA: 1.0% + 5 digits 3.270mA
30mA 0.01mA 0.010<1<32.70mA: 1.0% + 5 digits 32.70mA
30A 0.01A 0.05<1<50.0A: 1.0% + 5 digits 32.70A
60A 0.1A 50.0<1<60.6A: 5.0% + 5 digits 60.6A
 
AC Current Measurement (for 30032A)
Range Resolution Accuracy Maximum Allowable Current
3mA 0.001mA 0.010<1<32.70mA: 1.5% + 5 digits 3.270mA
30mA 0.01mA 0.010<1<32.70mA: 1.5% + 5 digits 32.70mA
30A 0.01A 0.05<1<50.0A: 1.5% + 5 digits 32.70A
60A 0.1A 50.0<1<60.6A: 5.5% + 5 digits 60.6A
 
• Zero correction:

3mA range:

displays 0.000mA (zero) when 0.010mA <1

30A range:

displays 0.00A (zero) when 0.05A<1
 
• Filter specification (for 30032A only)

Amplitude ratio at 100Hz:

-38dB (1.26%) or less (typical: -41dB)

Amplitude ratio at 120Hz:

-53dB (0.22%) or less (typical: -56dB)
 
 
 
Yokogawa Model 30031A and 30032A General Specifications
 

Parameter

Specification

Method of detection

Mean Value Detection and RMS-Value Calibration

Display

LCD (Digital display:3200 counts)
LCD (Bar-graph display: 32 segments)

Range Switching

Auto or manual range selection

Data Hold

On all ranges

Ambient Temperature and Humidity

0 to 50°C
80% RH or less (no condensation)

Temperature Coefficient

The following values must be added in the temperature range of either 30031A or 310032A
0 to 18°C or 28 to 50°
0<1<50.0A: ±(0.08% of reading/°C + 0.5 digits/°C)
50.0<1<60.6A: ±(0.3% of reading/°C + 0.5 digits/°C)

Influence of External Magnetic Field

0.0005% typical 1 (on current value of adjacent cable or wires)

Safety Standard

EN61010-1, EN61010-2-032 (CAT III 300V)

Circuit Voltage

300Vrms or less

Withstanding Voltage

3.7kV AC for one minute

Power Supply

One CR2032 (Coin-shaped) 3V battery

Battery Life

Approx. 90 hours (continuous)

Auto Power Off

Approx. 10 minutes after the last switch operation

Diameter of Measurable Conductor

40mm maximum

Dimensions

Approx. 70mm (W) x 179mm (H) x 25mm (D)

Weight

Approx. 200g

Accessories

User manual, Battery and soft Carrying Case

 

Home | Amprobe | CIE | Fluke | Kyoritsu-Kew |Megger | Reed | Yokogawa | Site Map | Search