SEW 6221EL Three Phase RCD Tester & Phase Sequence Indicator

SEW-Logo

The SEW 6221EL is a digital RCD tester for testing three phase and single phase RCD’s and also indicates phase rotation.

Built into a rugged case for field use, the SEW 6221EL is designed to test tripping time and tripping current of RCD’s and display the reading to the operator on it’s LCD display. The SEW 6221EL is easy to set up and easy to use.

pdf-6    SEW-6221-EL-Datasheet

If you would like more information regarding this product, simply email us here.
  • This field is for validation purposes and should be left unchanged.
Category: Tags: , ,

The microprocessor controlled SEW 6221EL is the ideal unit for testing trip current and trip time on both single and three phase RCD’s. It is designed to have  easy-to-use functionality, as tests consist of simple push button operation and a rotary dial for choosing the RCD current. On completion of the test the readings are then displayed on it’s LCD screen.

An additional feature of the SEW 6221 ELRCD tester is it’s built in phase sequence indicator, allowing the operator to quickly confirm by a visual inspection that all three phases are connected and live before conducting a test. The SEW 6221EL does not require a neutral conductor for testing as the fault current is routed via the earth connection in the meter, and it will work with 50Hz and 60Hz electrical systems with voltage of up to 550VAC (phase to phase).

SEW 6221EL Features:

  • Three Phase & Single RCD Test
  • Phase rotation indication
  • Phase presence indication
  • Microprocessor controlled for super fast results
  • Phase to earth voltage measurements
  • Comes in a rugged carry case
  • Rotary dial to select RCD current
  • Tests for disconnection time & disconnection sensitvity
  • Push button operation
  • Colour coded test leads

Specifications

Current Settings  999mAac / 50Hz-60Hz
Weight  3850g (batteries included)
Dimensions  330(L) × 260(W) × 160(D)mm
Batteries  1.5V “C” × 8 Bat OK Led = Vbat >9V
Current Resolution  1mA
Current Accuracy  ±3% ± 4mA
Timer Accuracy  1ms ± 4ms
Timer Resolution  1ms(Max. Time = 99.99s)
Over-Temperature Protection  Yes
Phase Polarity Trip Indicator  220Vac to 317Vac
Phase Start Selection  0° and 180°
Current Selection  Knob
Operating Temperature Range  0°C to + 40°C
Storage Temperature  -10°C to + 50°C
Protection Over Load:  550V(between all terminals)
Over Voltage:  Class III – 450V towards ground.
Phase Presence Nominal Voltage:  From 100Vac to 450Vac
Frequency Range:  From 10Hz to 400Hz.
Phases Rotary Field Direction Direction:  From 100 to 450Vac.
Frequency Range:  From 10Hz to 400Hz.

Complies to Safety Standards:

EN 61010-1 CAT III 550V EN 61326-1